The leak test is a mandatory measurement in accordance with TRGI for newly installed natural gas pipes. The measurement is explained here step by step using the DPG02 TOUCH.
the measurement as a video

Video on leak testing with the DPG02

In this video, Mr. Rau shows you the individual steps of the leak test with the RAU DPG02 TOUCH pressure tester.

Step by step

How the measurement is carried out

  1. Enter object / customer and inspector
  2. Fitting the single-pipe meter cap
  3. Connect Y-hose and test hose to DPG02
  4. On the display:“Check natural gas” and “Select system size” (under 100L | 100-200L | over 200L)
  5. Automatic measurement sequence starts:
    • Test pressure of 150 hPa is applied
    • 10 minutes fitting time
    • 10 minutes test time
  6. Measuring device beeps at the end of the measurement
  7. Print test report by tapping on the printer symbol

Note: The load test is carried out before the leak test. You can find many more helpful videos on our YouTube channel!